OCV Fire Pump Relief Valve

OCV fire pump relief valves limit pump discharge pressure to protect fire pump systems. Two models are offered: the 108-2HP/108-2HPA for high relief settings (200–740 psi) and the UL listed, FM approved 108FC/108FCA (60–300 psi). Both are pilot-operated with a field-adjustable setting. Features & Benefits Opens quickly and holds pressure within close limits Pressure setting adjustable with a single screw Factory tested and pre-set to your requirements Suitable for water and seawater Globe or angle pattern, 3″ to 8″ Applications Fire pump discharge protection and fire suppression systems Petrochemical, oil and gas, onshore and offshore Tunnels and mining Power generation, transformer and transmission plants

Share

Product Details

Technical Specifications

SpecificationOCV 108-2HP / 108-2HPAOCV 108FC / 108FCA
ManufacturerOCV Control Valves, Tulsa, Oklahoma, USA
Valve TypePilot-operated fire pump pressure relief valveSingle-seated, line-pressure-operated, diaphragm-actuated, pilot-controlled relief valve; main valve is the OCV 65 basic control valve
Body PatternGlobe (108-2HP) or angle (108-2HPA)Globe (108FC) or angle (108FCA)
Size Range3″ to 8″ (DN80 to DN200)3″, 4″, 6″, 8″ (DN80, DN100, DN150, DN200)
End ConnectionsANSI flanged Class 300#
300# inlet × 150# outlet
ANSI flanged Class 150#, Class 300#
300# inlet × 150# outlet
Relief Setting Range200 to 740 psi (13.7 to 51.0 bar), field adjustable60 to 180 psi (4.1 to 12.4 bar) or 100 to 300 psi (6.9 to 20.7 bar)
Pressure Rating / Maximum Setting740 psi for Class 300# and 300# × 150#
Maximum working pressure by body material: ductile iron 640 psi; steel and stainless steel 740 psi; bronze 500 psi (3″ size)
Maximum setting, UL: 300 psi (3″, 4″, 6″); 175 psi (8″)
Maximum setting, FM: 175 psi (3″ to 8″)
Maximum Pump Flow3″: 500 GPM
4″: 1,000 GPM
6″: 2,500 GPM
8″: 5,000 GPM
3″: 500 GPM (114 m³/h)
4″: 1,000 GPM (227 m³/h)
6″: 2,500 GPM (568 m³/h)
8″: 5,000 GPM (1,136 m³/h)
Sized per NFPA 20
Temperature Range (by Elastomer)Buna-N: 32 °F to 180 °F
EPDM: 32 °F to 230 °F
Buna-N: 32 °F to 180 °F
EPDM: 32 °F to 230 °F
Body MaterialStandard: ductile iron
Optional: cast steel, stainless steel, NAB
Standard: ductile iron
Optional: stainless steel, cast steel, NAB
Trim MaterialsSeat ring: bronze standard; stainless steel or NAB optional
Stem: stainless steel standard; Monel optional
Spring: stainless steel standard; Elgiloy or MP35N optional
Pilot and tubing/fittings: stainless steel
Seat ring: bronze standard
Stem: stainless steel (Monel optional)
Spring: stainless steel
Pilot: bronze (NAB optional)
Tubing: copper with bronze/brass fittings (stainless steel optional)
ElastomersDiaphragm and seat disc: Buna-N standard, EPDM optionalDiaphragm and seat disc: Buna-N standard, EPDM optional
CoatingFire red epoxy on body and bonnet (per engineering specification)Internal ferrous surfaces epoxy coated
External surfaces epoxy coated and painted fire red
FluidsWater and seawaterWater, seawater and foam
Seat LeakageANSI FCI 70-2 Class VIANSI FCI 70-2 Class VI
Certifications and ComplianceABS Type Approval
Fire tested to EN ISO 19921
UL Listed (QXZQ)
Factory Mutual (FM) Approved (1361 and 1363)
ABS Type Approval
Lloyd’s Register Approval

Related Products

placeholder
ARCA-Hygienic-Control-Valve-BIOVENT
ocv-115-22-terminal-solenoid-shut-off-valve
AMOT ASX-350 Self-Exciting Flameproof Alternator

Product Enquiry

Product Name

OCV Fire Pump Relief Valve

What would you like to enquire about? (Please tick all that apply)